Two new methods, Current Change Ratio (CCR) and Percentage Area Difference (PAD) were proposed to solve a problem of how to distinguish between internal faults and inrush condition when transformer is switched on. This problem may delay operation or may mal-operate some protection schemes like deferential protection. The methods were concluded after observing and analyzing the behavior and shape of large number of both inrush and internal fault signals that had been obtained using a model transformer in a laboratory. The methods were practically tested on a three phase transformer with rated power of 20kVA at Cardiff University's laboratory and the data were processed using LabVIEW and MATLAB programs. The results showed that internal faults can be correctly distinguished from inrush condition within a short time (from 5ms to 10ms), particularly the minor internal faults such as the inter-turn fault which is submerged to inrush current and make it is too difficult to be detected. The advantages of these algorithms are simple in design and faster than the second harmonic method which is the most popular method used for solving this problem.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.