Summary
In this paper, by decomposing high‐frequency band of differential current using wavelet transform and giving the extracted features to the empirical mode decomposition method, internal faults from magnetization conditions in power transformers are discriminated. The merit of the suggested method is validated by various simulation results using PSCAD and practical data set gathered from a laboratory 3‐phase transformer. Internal faults could be precisely discriminated from magnetizing current in half cycle of the fundamental frequency; this is one advantage of the method. Also, an innovative technique is suggested to tackle current transformer saturation negative impacts on differential relays. At end, the method is assessed and compared with some other well‐known discrimination methods by plenty of simulations and experiments.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.