Many things can affect the Net Plant Heat Rate (NPHR) value, including operating parameters, fuel and equipment’s condition. The performance target of NPHR for Kaltim Teluk CFB CFPP based on specifications is 3430 kCal / kWh. Operational data shows that the NPHR of Unit #1 and Unit #2 is higher then the performance target. Analysis of operation and maintenance data showed that the low average net load and high condenser back pressure are the dominant problems that caused heat loss. One way to minimize heat loss and improve NPHR performance can be done by maximizing debris filter cleaning process through adjusting valve opening angle which can reduce differential pressure and finally reduce the backpressure at the condenser. With the flow simulation inside the debris filter, in order to achieve maximum flow rate with acceptable erosion rate, the optimum cleaning reached at valve opening angle 75°-60° and with this cleaning method, heat loss can be reduced 14.96 kCal/kWh and 50.09 kCal/kWh for unit #1 and unit #2 respectively.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.