In this paper, experimental investigations of a two-phase thermosyphon loop are presented in order to keep telecommunication equipments temperature below 55°C. The experimental setup consists of a thermosyphon loop containing an evaporator and a condenser connected by two flexible tubes. Tests are performed firstly in transient state using the thermosyphon loop prototype inside telecommunication cabinet. The n-pentane is used as the working fluid. Firstly, transient thermal characteristics of the thermosyphon loop are measured. In the other way, the thermosyphon loop is tested for different power input up to 450W. Operating temperatures of the telecommunication equipments cooled with forced air convection and two-phase thermosyphon loop are compared.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.