The ventilation rates of 23 operating theatres were tested randomly. These were found to vary widely from design specifications (--43 to +40%). One modern theatre was studied intensively for 6 months and the causes of poor ventilation determined. Preventative maintenance schemes are justified by a positive relationship with plant performance. The influence of theatre ventilation of contamination with anaesthetic agents and the medico-legal implications of poor theatre ventilation are discussed. There is a need for main duct airflow signals, displayed in theatre, to warn personnel of low levels of theatre ventilation.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.