There are various types of distributed generators (DGs) with different grid integration strategies. The transient characteristics of the fault currents provided by the DGs are different to those of conventional synchronous generators. In this paper, a distribution network with multi-type DGs is investigated, including consideration of DG low-voltage ride through (LVRT). The fault current characteristics of two typical DGs, i.e. an inverter-interfaced distributed generator (IIDG) and a doubly-fed induction generator (DFIG), are analyzed, considering the specific operation modes. Based on analysis of the fault characteristics, an equivalent model of the multi-type DGs under symmetrical/asymmetrical fault conditions is established. A fast-iterative fault calculation method for enhancing the calculation efficiency while avoiding local convergence is then proposed using an improved particle swarm optimization (PSO) algorithm. A simulation system of the distribution network with multi-type DGs is established in PSCAD/EMTDC. The simulation results validate the high accuracy and calculation efficiency of the proposed calculation method of the fault components. This can assist in the settings of the protection threshold.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.