-Influence of moisture on the instrument transformers' paper-oil insulation and its further maintenance is described in this paper. Improved insulation drying method using vacuum and temperature regulation with definite regulation algorithm of parameters is proposed and analyzed by comparing it with conventional drying method.
-Measuring techniques of dielectric losses tanδ of high voltage equipment are discussed and compared in this paper. There are several methods for determining tanδ and capacitance values in high voltage substation on site.Simple measuring methods like GST and UST can be put into practice without result corrections in ideal conditions. However electrical field in substation originates negative affect on measuring results, therefore different connection schemes of measuring methods have to be used.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.