At the Cikalong hydropower plant there are 3 power transformers with a voltage rating of 6.3/77 kV, because of their long life, it is necessary to analyze the condition of the transformer oil. One way to determine the level of fault gas contained in transformer oil is the DGA (Dissolved Gas Analysis) test. DGA will extract the gas to find out indications of disturbance based on the interpretation of the dissolved gases data, namely the Total Dissolved Combustible Gas (TDCG), Key Gas, Roger's Ratio, Doernenberg's Ratio and Duval's Triangle methods. This method is in order to determine the condition of the transformer oil is normal or not, measure the breakdown voltage value and calculate the correlation value between operating hours and the amount of power production. The results of the DGA analysis on transformer units 1, 2, and 3 of the Cikalong hydropower sub-unit show the TDCG value in condition 1, which includes all transformers in good condition. The value of the correlation coefficient between hours of operation and the number of kWh production with TDCG is 0.267 and 0.297, respectively, which indicates the relationship between these variables is a weak relationship (standard value is close to 1).
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.