A comprehensive survey to determine the occupational radiation exposure in water supplies and spas was conducted in the federal state of Upper Austria. The study comprises 45 water supplies. The limit for radon exposure of 6 MBq h m(-3) was exceeded by two water supplies (WS 33 and WS 42). In one water supply (WS 29), the level of 2 MBq h m(-3) was exceeded. These water supplies were mitigated. Prior to mitigation the main radon sources were identified. Mitigation measures were: evacuation of the outlet air of the vaporiser by means of a fan, installation of a fan in the exhaust air duct of the compensating reservoir, sealing of drain shafts and mechanical ventilation of the office. In all water supplies, the radon exposure was reduced to below 0.8 MBq h m(-3) at a cost of approx. euro 750 to euro 1000.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.