This paper presents the results of laboratory tests of cellulose insulation drying with the use of synthetic ester. The effectiveness of the drying process was investigated depending on the initial moisture of cellulose samples (2%, 3%, and 4%), ester temperature (55, 70, and 85 °C), initial moisture of the ester (70, 140, and 220 ppm), drying time (48, 96, and 168 h), and the weight ratio of cellulosic materials to ester (0.067 and 0.033). A large influence of temperature and time of drying on the efficiency of the drying process was found. This is important information due to the application of the results in the transformers drying procedure. The heating and drying ester unit should provide the highest possible temperature. For the assumed experiment conditions the initial moisture of the ester had little effect on the drying efficiency. An ester with a moisture content below 140 ppm can still be considered as meeting the requirements for drying cellulose with significant moisture. The weight ratio of cellulose products to ester has no major effect on drying efficiency during cellulose drying by circulating dry ester.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.