Synchronous generators were manufactured with asphalt bonded, mica flake insulation from 1917 to the 1950's.There is a large fleet, perhaps two thousand, of these machines still in service today. This paper presents the results of a well documented series of field tests, many to failure, on 20 asphalt-mica insulated fossil and hydro synchronous generators on the American Electric Power system and laboratory tests on over 30 spare asphalt-mica stator bars and coils at AEP's Dolan Laboratory.The paper clearly shows that a straightforward ac overpotential test and a simple graphical evaluation and analysis can be used to confidently determine the remaining service life of asphalt bonded, mica flake insulated synchronous generators that have been well maintained and operated within design limits.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.