TVA identified an increasing failure rate of 132-kV (106-kV Maximum Continuous Operating Voltage) porcelain arresters on the 161-kV system. A cross-organizational team was formed to determine the root cause of the 19 arrester failures and provide solutions. The team researched arrester failure modes and solicited input from arrester experts. A root cause diagram is discussed and multiple failure modes were ruled out. Multiple failed arrester units were dissected indicating moisture ingress as the root cause leading to the recent failures. Computer simulations contrasted faults through the Metal Oxide Varistor (MOV) block stack versus faults flowing through the air cavity surrounding the MOV stack. All 19 failures were recorded by digital fault recorders (DFR). The DFR waveforms were compared to the computer simulations showing that the arresters flashed over the internal air cavity. Based on the available physical evidence, moisture ingress is the likely root cause issue for the failures from 2002 to date.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.