In order to locate the single-phase-to-ground fault in distribution network, a research method of single-phase-to-ground fault location and recovery technology in distribution network is proposed. According to the characteristics of single-phase-to-ground fault in distribution network, the fault characteristics of zero-sequence current and three-phase current transient records are extracted by generalized S transform of correlation coefficient, and multi-source redundant information is formed. Fuzzy C-means clustering analysis method is used to fuse multiple fault features online location strategy. The simulation results show that the fuzzy clustering based on FCM changes continuously with the accumulation of samples, and the sample center changes with the enrichment of the samples. When the arc suppression coil is grounded with different initial phase angle transition resistance and intermittent fault, the state of each measuring point can be correctly identified, and the accurate energization rate is 97%. The test results show that the system can achieve accurate positioning for all sections.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.