Abstract:Interest has risen among utilities in using natural ester (NE) insulating oils in transformers as a substitute for conventional mineral oil. However, present understanding on aging behaviour of NE-paper composite insulation system and knowledge on application of existing condition monitoring tools for NE-based insulation are inadequate. This limits the cost effective and reliable field applications of NE insulating oil. To pave the way the application of NE-based insulation in transformers, a systematic study has been performed to compare the aging behaviour of transformer grade pressboard (PB) impregnated in NE and conventional mineral oil. Applicability of a number of chemical and physical parameters, including acidity value, dielectric dissipation factor (DDF), viscosity, and colour for assessing the quality of NE insulating oil is also discussed in this paper. Comparisons are made based on the limiting values provided in the related IEEE Standard and properties of mineral oil under similar aging conditions.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.