The noise in substations has become one of the most concerning problems in the field of power grid. In this paper, the principle of substation layout optimization based on the maximum acoustic ray shielding method is established in the premise of the sound wave propagation rule in complicated air medium to meet the requirements of relevant national environmental standards for noise at the boundary of the substation. By establishing the acoustic simulation analysis model of the 220kV outdoor substation, the noise level at the boundary of the substation before and after the layout optimization is compared and analysed, and the distribution rule of the sound field inside and outside the substation is obtained. The analysis results show that the optimized layout of the substation can effectively reduce the noise at the boundary of the substation, which provides a control method for the noise optimization design of the substation.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.