Abstruct-The paper presents a new method of taking into account overlapping zones in stacked transformer cores for magnetic field calculations. The method has been worked out with the use of homogenization technique under the assumption that the distribution of magnetic flux between the layers of overlaps results from the tendency to reach the minimum of the magnetic field energy. This enables replacement of a heterogeneous 3-D overlap structure with a simpler homogeneous 2-D one. The method has been used to calculate equivalent homogenized reluctivity of the whole structure and flux density vectors in its layers. The family of equivalent anisotropic magnetizing curves of an overlap has also been determined. To discuss the method, a classical overlap of a transformer core has been chosen. Calculation results and the results of measurements taken in two adjacent sheet layers of an overlap situated in a T-joint of a 3-limb 3-phase transformer core have been compared and are presented in the paper.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.