This paper presents a double conversion Uninterruptible Power Supply (UPS) system with input voltage equal to 110Vac/220Vac and 24Vdc battery-set. To attend these features, a four-port circuit based on High-Frequency Transformer (HFT) isolated is employed, which consists in two input ports (grid side and battery source side) and two output ports (inverter side and battery-charger side). This topology is suitable for on-line single-phase UPS systems with limited range of power applications (≤ 2kVA). Due competitive market, an opportunity to develop a new UPS with highfrequency isolation and low cost is very attractive to replace the old UPS systems isolated in low-frequency, heavy and bulky. The principle of operation and simulation results, for Vi=110Vac/220Vac; Vb=24Vdc; Vo=110Vac; So=1000VA e fo=60 Hz, are presented.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.