Controlled switching system (CSS) with a 204 kV gas circuit breaker (GCB) demonstrates to reduce an inrush current and to eliminate re-ignitions in shunt reactor switching. Target closing and opening instants for controlled switching are determined by the electrical and mechanical characteristics of GCB. Idle time dependence of the operating time, which gives a sufficient impact on controlling accuracy, is evaluated and successfully compensated by synchronous switching controller (SSC). Field operation of CSS for a year shows an effective suppression of inrush current on closing and prevention of re-ignitions on opening of shunt reactor. The operations also proved that the CSS has a satisfactory performance for electro-magnetic disturbance imposed in practical field. GCB
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.