This paper presents a practical experimentation for comparing reactive/non-active energy measures, considering three-phase four-wire non-sinusoidal and unbalanced circuits, involving five different commercial electronic meters. The experimentation set provides separately voltage and current generation, each one with any waveform involving up to fiftyfirst harmonic components, identically compared with acquisitions obtained from utility. The experimental accuracy is guaranteed by a class A power analyzer, according to IEC61000-4-30 standard. Some current and voltage combination profiles are presented and confronted with two different references of reactive/non-active calculation methodologies; instantaneous power theory and IEEE 1459-2010. The first methodology considers the instantaneous power theory, present into the advanced mathematical internal algorithm from WT3000 power analyzer, and the second methodology, accomplish with IEEE 1459-2010 standard, uses waveform voltage and current acquisition from WT3000 as input data for a virtual meter developed on Mathlab/Simulink software.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations –citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.