-In this paper, we propose a electrical/mechanical method to effectively diagnose the local deterioration of a 10m long power shielded twist pair cable defined by the American Wire Gauge (AWG) 14 specification using electrical/mechanical methods. The rapid deterioration of the cable proceeded by using the heating furnace, which is based on the Arrhenius equations proceeds from 0 to 35 years with the deteriorated equivalent model. In this paper, we introduce a method to diagnose the characteristics of locally deteriorated cable by using S 21 phase and frequency change rate measured by vector network analyzer which is the electrical diagnostic method. The measured S 21 phase and rate of change of frequency show a constant correlation with the number of years of locally deteriorated cable, thus it can be useful for diagnosing deteriorated cables. The change of modulus due to deterioration was measured by a modulus measuring device, which is defined by the ratio of deformation from the force externally applied to the cable, and the rate of modulus change also shows a constant correlation with the number of years of locally deteriorated cable. Finally, By combining the advantages of electrical/ mechanical diagnostic methods, we can efficiently diagnose the local deterioration in the power shielded cable.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.