The components of active power losses in long-distance AC power transmission are investigated. It is shown that in the modes of low and medium loads the main share of losses are corona losses. The imperfection of the current method of determining the corona power losses, which are climatic in nature, determines the method of separating these losses from the total after calculating the load power losses. A four-component formula for determining the load losses of active power is obtained. It is shown that to clarify the calculation model it is necessary to take into account the actual temperature of the wire, taking into account changes in weather conditions along the route of the line. The results of calculation of components of active power losses in the 750 kV overhead transmission line "Zakhidnoukrainska-Vinnytska" during the day of September 13, 2021 are given. References 9, figures 4, tables 3.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.