Transient state estimation (TSE) was used to determine the state values that have no measurement equipment placed in an electric power system with transient phenomena. Previous papers used the PI model for TSE with a short transmission line, but longer lines require the development of algorithms that include the distributed parameters of transmission lines with the Bergeron model. The test system was a 10-bus power system. The simulated transient was caused by a fault event, resulting in different persistent voltage drops that ranged from 10% to 90% at selected buses. In addition, noises were applied to evaluate the algorithm, which was defined to be normally distributed. Noise at 1%, 2%, and 3% was added to all measurements. The results showed that the developed TSE provided good estimation at the locations that had no measurement equipment for distributed transmission lines.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.