Over more than 30 years development of Non-intrusive Load Monitoring (NILM), many technologies were developed from sampling frequency I Hz to hundreds kHz to extract from simple information such as difference power dP, dQ; shape of transient signatures to complex information such as harmonics or electromagnetic interference (EM I). There are now many real NILM systems in residential applications but there is lack of researches to apply NILM to commercial and industrial application. This site uses so much energy in business and production so that analyzing power consumption to optimize their operation is very important to produce competitive products on the market. Unfortunately, it is very difficult to recognize commercial and industrial machine that are composed of many electric elements. This paper provides a new NILM approach to monitor commercial and industrial machines based on basic electrical appliances inside architecture of machine. All power differences dP, dQ, dS are used to analyze and classify basic electrical appliances. Adaptive filter CUSUM is used to improve removing noise in preprocessing phase of the NILM system. Finally, Field Program Gate Array (FPGA) is discussed to implement our NILM system.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.