Medium-voltage circuit breakers can fail to interrupt three-phase fault currents when power systems have transient recovery voltage (TRV) characteristics which exceed the rating of the circuit breaker. This paper examines the application of 13.8-kV generation and load switchgear for an oil refinery in which circuit parameters as originally designed would have exceeded the 13.8-kV circuit breakers' TRV ratings had corrective measures not been taken. This paper illustrates this case and discusses the basis of TRV, how TRV is assessed, and alternative actions taken to bring circuits to within the 13.8-kV circuit breaker ratings.Index Terms-EMTP, medium voltage circuit breaker, transient recovery voltage.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.