GE Energy Services VBster& Petrolewnkemi AB GE Energy Services F6segelv. 28, SE-723 48 V b t e d s SWEDEN SWEDEN lars.arvidsson@,petroroleumkemi.se SWEDEN Programma Electric AB Eldarv 4, SE I 8 7 75 Taby Programma Electric AB Eldarv 4, SE 187 75 Taby -roberts.neimanis@ps.ge.com
AbsIractFrequency domain dielectric spectroscopy, measurements of capacitance and dissipation factorlpower factor in a wide frequency range becomes increasingly popular in assessment of power transformer insulation systems. The interpretation ofthe measurement results is mostly made using a simple model taking the relative amount of oil and impregnated cellulose paper into account. This paper presents main findings from frequency domain dielectric spectroscopy measurements on transformer oil samples from different power transformen still in service.The interpretation model using oil permittivity o f 2 2 combined with its conductivity is eompared with actual measurements in the frequency range of 1000 Hz down to 0.01. sometimes down to 0.001 Hz. The temperature dependence and possible voltage dependence, especially at lower frequencies, are also investigated.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.