MemberThis paper presents the analysis and design of a shunt hybrid active filter for harmonic damping in a 6.6-kV power distribution system. This hybrid filter has been proposed and tested experimentally with a 200-V, 20-kW laboratory system, showing good damping performance. Another possible solution for harmonic damping is to install a shunt pure active filter at the end of a feeder. However, the pure filter is too costly and bulky to be installed in a 6.6-kV system. This paper discusses the design criteria for a hybrid filter intended for installation on a 6.6-kV power distribution system. Detailed comparisons between the pure filter and the hybrid filter are also included as a foundation for the design of the hybrid filter. The performed design confirms the feasibility of installation of the hybrid filter on a 6.6-kV power distribution system.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.