When de-energizing shunt reactors with load interrupters, reignitions are likely to occur. The resulting high frequency transients have been investigated for a typical EHV installation by computer studies and field tests. These transients can be eliminated or minimized by controlling the instant of contact parting. They can also be reduced by low ohmic opening resistors. The dielectric requirements for BPA's 500-kV shunt reactor installations are discussed. It is shown that even in installations with reduced insulation levels routine
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.