Liberalization of the energy market drives utilities to a more cost-effective power system. Power transformers are the most complex, important, and critical components of the transition and distribution power systems. Insulation system is the key component of life extension, better availability and higher reliability of a transformer. In order to achieve both decreasing operational cost and reliable service condition-based maintenance is needed. Monitoring and diagnostics methods and techniques, for insulation condition assessment of power transformers, are described. Date base and knowledge rules diagnostics management system, in internet oriented environment, is outlined. .
The paper describes an intercomparison of measuring systems for current transformers accuracy testing between three laboratories Koncar -Instrument Transformers, Koncar -Electrical Engineering Institute and Electrical Engineering Institute Nikola Tesla. All laboratories are accredited according to EN/ IEC 17025: 2017 standard. The obtained discrepancies in ratio and phase errors are within participant's declared measurement uncertainties. All laboratories have confirmed their competence (|E n |≤1) for the applied measurement methods, in accordance with EN ISO/ IEC 17043.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.