The paper presents experimental data and results from a prediction tool for the performance of a desiccant loop cooling system. The experiments are performed under a variety of high humidity and hot ambient conditions and the system performance is described. One of the experimental conditions is typical of many Indian cities and the systems appropriate for those cities are established. A simulation program that can predict the performance of the desiccant loop is developed. The simulation results show that this system can work as effectively as vapor compression air-conditioning for certain ambient conditions whereas it can function as a pre-cooler to a vapor compression system under more severe conditions, resulting in a reduced power consumption. The results presented in the paper give a guideline to practicing engineers as to when a desiccant loop cooling system would be useful. A simple payback analysis and a lifecycle cost analysis shows that a desiccant cooling system with a waste heat recovery recuperator is an economically viable investment.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.