So far, the importance for an accurate load model has been constantly raised and its necessity would be further more emphasized. Currently used load model for analysis of power system in Korea was developed 10 years ago, which is aggregated by applying the statistically estimated load compositions to load models based on individual appliances. As modern appliances have diversified and rapidly changed, the existing load model is no longer compatible with current loads in the Korean power system. Therefore, a measurement based load model is more suitable for modern power system analysis because it can accurately include the load characteristics by directly measuring target load. This paper proposes a ZIP model employing a Kalman-filter as the estimation algorithm for the model parameters. The Kamlan-filter based parameter identification offers an advantage of fast parameter determination by removing iterative calculation. To verify the proposed load model, the four-secondinterval real data from the Korea Energy Management System (K-EMS) is used.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.