In order to understand the variation of ammonia as a cooling refrigerant, the ammonia coolant is being used in power plant air cooling system. The subcooled boiling phase transformation of ammonia in a horizontal pipe tube was simulated through the application of the CFD fluid computational platform, the fluid state parameters in the tube were given at the same time. The speed variation along the axis of the tube was obtained, the speed is increasing, the Reynolds number corresponding substantial increase in the convective heat transfer coefficient corresponds to raise; The vapor volume fraction and boiling heat transfer coefficient along the tube were obtained. The boiling can strengthen the heat transfer significantly. The results showed that the ammonia as a cooling refrigerant by raising the Reynolds number and the use of the latent heat absorb these dual characteristics to improve the heat transfer coefficient is worth promoting.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.