To exploit high wind conditions, wind turbine generator systems are constructed in places with few tall structures; as a consequence, they are often struck by lightning. This results in breakdown and malfunction of electrical, communications, and control systems inside and adjacent to the wind turbine generator system because of ground potential rise. Impulse tests were conducted on an actual wind turbine generator system and analytical surveys based on field tests were carried out using electromagnetic field analysis. The ground potential rise of the system and that around its foundation was measured and analyzed. The grounding system employed in this study consisted of the foundation, grounding mesh, and foundation feet. The frequency characteristics were calculated using the Laplace transform to get voltage responses for all types of lightning current waveforms.Step and typical lightning current waveforms were used to calculate potential rise responses.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.