The objective of this paper is to integrate five traditional criteria of the Dissolved Gases Analysis published in different standards into a more reliable approach of the fault diagnosis of power transformer for maintenance personnel of Taiwan Power Company(TPC). This paper employs Fuzzy Inference System(FIS) to develop two factors as a integrated fault diagnosis for power transformer. One is the identifiable factor which interprets the fault type, the other is the fault factor which asseses the operating condition of transformer. The result of diagnosis can be observed by web browser on TPC intranet. The designed synthetic method has been verified by TPC historical transformers gas records and shows its effectiveness in transformers diagnosis.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.