In this paper, we studied on the detection of series arcing which is a main cause of electrical fires in low-voltage indoor wiring system. To distinguish series arcing state from normal one, we proposed a detection method based on that the magnitude of arc voltage included in AC voltage varies at random during series arcing. We designed and fabricated a highpass filter with the low cut-off frequency of 3kHz to attenuate AC voltage by -80dB or below, and to pass arc voltage without distortion. Also, a phase shift algorithm which eliminates the periodic component of arc voltage was used for nonlinear loads like incandescent lamps controlled by a dimmer.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.