In November 1981, a waterborne giardiasis outbreak occurred within the Highlands Water and Sanitation District in Colorado. Although the immediate cause of the outbreak was reduced chlorine contact time because of a pump failure, numerous design and operational deficiencies existed at the plant. Lack of chemical pretreatment, improper backwashing procedures, poor application of raw water to the filter, and failure to monitor plant conditions all contributed to the outbreak. Turbidity and bacteriological records did not indicate any problems, confirming the crucial role of proper design, installation, and operation of the multibarrier technique in preventing waterborne giardiasis outbreaks. Giardiasis is an intestinal disease most
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.