Abstract-The method of voltage sag source location proposed in this paper is using wavelet-multiresolution to decompose the voltage and current waveforms from monitoring points and analyzing the change of signal energy of three-phase instantaneous power during voltage sag to ascertain the sag source location relative to the monitoring points. The location of voltage sag caused by line fault, transformer energizing and induction motor starting, which are the main reason of sag, are analyzed and tested using this method based on an PSCAD simulation model in this paper. The results show that the method is simple and reliable and can be used to determine sag source location.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.