Abstract:China Machinery Industry Standard (CMIS) GB/T 12326-2008 prescribed in the islanded operation mode, microgrid inverter (MGI) output voltage dynamic transient range is less than 10% when the resistive load is switched rapidly between 0% and 100%. The three-loop power virtual synchronous generator (VSG) control methods are commonly used in MGI units to share the loads among the parallel MGIs. However, the transient output voltage of the MGI is beyond the CMIS when the resistive load steps sharply. In order to me… Show more
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.