Abstract:This paper is exploring requirements for the line current differential function (87L) with regards to the tolerance to current transformer (CT) saturation. Typically, requirements provided by the manufacturers or standards are to eliminate CT saturation completely by proper sizing of CTs, which is not always practical.First, the general knowledge of CT fundamental and saturation is introduced, including CT circuit model, simulation model, AC saturation, DC saturation and factors driving CT into saturation. The… Show more
“…CT calculations are normally carried out to assure that the CT will not saturate in the case of external faults [30]. On the other hand, it is expected that the CT may saturate in the case of severe internal faults.…”
Section: G Effect Of Current Transformer (Ct) Saturationmentioning
“…CT calculations are normally carried out to assure that the CT will not saturate in the case of external faults [30]. On the other hand, it is expected that the CT may saturate in the case of severe internal faults.…”
Section: G Effect Of Current Transformer (Ct) Saturationmentioning
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.