Detrapped Charge-Affected Depolarization-Current Estimation Using Short-Duration Dielectric Response for Diagnosis of Transformer Insulation

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
3
2

Citation Types

0
5
0

Year Published

2021
2021
2024
2024

Publication Types

Select...
3
3

Relationship

1
5

Authors

Journals

citations
Cited by 15 publications
(5 citation statements)
references
References 21 publications
0
5
0
Order By: Relevance
“…According to the basic principle of PDC test, if the model parameters can be identified only by polarization current spectral lines, the test time can be halved, and the power outage time of the field test can be greatly reduced. The research results of reference [14] showed that the dielectric response analysis and parameter calculation results using only polarization current and using polarization/depolarization current at the same time are consistent, which verifies the rationality and effectiveness of polarization current as the original data.…”
Section: Introductionmentioning
confidence: 59%
“…According to the basic principle of PDC test, if the model parameters can be identified only by polarization current spectral lines, the test time can be halved, and the power outage time of the field test can be greatly reduced. The research results of reference [14] showed that the dielectric response analysis and parameter calculation results using only polarization current and using polarization/depolarization current at the same time are consistent, which verifies the rationality and effectiveness of polarization current as the original data.…”
Section: Introductionmentioning
confidence: 59%
“…Fig. 4 shows the typical profile of polarization and depolarization current (PDC) [8], [13]. Keithley 6517B Electrometer is used for field test to get data from real-life transformer.…”
Section: Assessment Of Insulation Condition Using Pdc Anaysismentioning
confidence: 99%
“…Other Parameters, such as the Dielectric Absorption Ratio (DAR), which measures the insulation resistance at 60 seconds to 30 seconds, and the Polarization Index (PI), which measures the insulation resistance at 600 seconds to 60 seconds, are also used to determine the state of the insulation. These parameters can be obtained directly from the measured PDC data [8]. Therefore, if the polarization current is affected by the residual dipole energy or any other field issues, the above described performance parameters wrong information regarding the insulation condition.…”
Section: Assessment Of Insulation Condition Using Pdc Anaysismentioning
confidence: 99%
See 1 more Smart Citation
“…The literature emphasizes the importance of time domain analysis techniques, such as PDC analysis concerning transformer oil-paper insulation, serving as a pivotal aspect of effective insulation assessment 7 . Diverse traditional insulation modeling techniques encompassing the conventional Debye mode (CDM) and the modified Debye model (MDM) provide a unique characterization of transformer insulation systems 8 , 9 . Furthermore, advanced techniques such as the model with time-varying parameters (MTVP) and the modified Maxwell model (MMM) provide a foundation for sophisticated methodologies to comprehend and evaluate insulation performance 10 .…”
Section: Introductionmentioning