In order to avoid SARS-CoV-2 transmission inside educational buildings and promote the safe reopening of schools, the Italian Government, in line with the other European countries and in accordance with the WHO recommendations, adopted a contingency plan including actions able to guarantee adequate air ventilation in classrooms. Therefore, in this pilot study, a surveillance activity based on the real-time monitoring of CO
2
levels as a proxy of SARS-CoV-2 transmission risk, was conducted inside 9 schools (11 classrooms) located in Apulia Region (South of Italy) during the reopening of schools after the lockdown due to COVID-19 pandemic. More specifically, monitoring activities and data treatment were conducted to evaluate the initial scenario inside the classrooms (first stage of evaluation) and the potential improvements obtained by applying a detailed operating protocol of air ventilation based on specific actions and the simultaneous real time visualization of CO
2
levels by non-dispersive infrared (NDIR) sensors (second stage of evaluation). Although, during the first evaluation stage, air ventilation through the opening of windows and doors was guaranteed, 6 (54%) classrooms showed mean values of CO
2
higher than 1000 ppm and all classrooms exceeded the recommended CO
2
concentration limit value of 700 ppm. The development and implementation of tailored ventilation protocol including the real time visualization of CO
2
levels allowed to depict better scenariosAn overall improvement of CO
2
levels was indeed registered for all classrooms where teachers were compliant and helpful in the management of the air ventilation strategy. Therefore, this study reports the first evidence-based measures demonstrating that, with the exception of few environments affected by structural limits, the real-time visualization and monitoring of CO2 concentrations allowes effective air exchanges to be implemented and contributes to prevent SARS-CoV-2 transmission. Moreover, on the basis of the monitoring outcomes and in order to ensure adequate air ventilation in educational buildings, a 4 level-risk classification including specific corrective actions for each level was provided.