Evaluating the Precision of the DC Decay Test Method for Characterizing Wound-Field Synchronous Machines in Power Plants

Frederic Maurer,
Thomas Øyvang,
Jonas Kristiansen Nøland

Abstract: The sudden short-circuit test is the gold standard for determining the equivalent diagram of wound-field synchronous machines (WFSMs). Only a single measurement is needed while the machine is in saturated mode. However, this destructive test can significantly reduce the lifetime of the stator winding. Moreover, determining the equivalent diagram in the q-axis is more complicated and is often not performed. DC-decay tests are low-power alternatives that allow for the determination of the equivalent diagram in b… Show more