“…According to the Guideline, the three parameters should respectively fall below ± 10%, 30%, and above 0.75 for models calibrated against hourly measurements. Nonetheless, when it comes to historic construction, it is common practice to consider the model as calibrated once it complies with the restrictions on the first two parameters only [45][46][47][48]. In this study, the model was considered calibrated when the quantification of errors complied with ASHRAE limits CV RMSE < 5% and NMBE < 20%.…”