Fault Prediction Based on Unbalanced Current Detection of Three Phase Heater and Selection of the Protective Device

Abstract: Three phase heaters in 7 buildings of 2 sites were examined for precise diagnosis. The sample size was 626. Precise examinations of current and the heater wiring status revealed contact failures and arcs in equipments that had CUF larger than 10%. Contact failures and arcs may cause electrical fire. Therefore, the correlation between the CUF and the imperfections in heater equipment and its wiring was analyzed for three phase heaters. In addition, the protection devices used for detection of heater imperfectio… Show more