Abstract:Abstract. The paper presents the results of studies on the harmonic active and reactive power at nodes of 110 kV and 220 kV networks. The studies were based on the measurements made at the node of 110 kV network supplying power to an aluminum plant and at the node of 220 kV network supplying power to railway traction substation. The supply networks belong to the Unified Energy Systems of Russia. Many other facilities with high-power nonlinear loads receive electric energy from these networks. They make their c… Show more
“…In the last decade intensive measurements of harmonics parameters have been continued, which is explained by the emergence and widespread use of new nonlinear electric equipment and increase in the values of current and voltage harmonics in the networks. For example, the results of measurements at the network node supplying the nonlinear loads of the retransmission TV stations are presented in [8]; the results of measured parameters of the harmonics generated by energy saving lamps are presented in [9]; the harmonics measured in the medical center and their impact on the work of the medical equipment are indicated in [10]; the results of large-scale measurements of power quality indices in the 110 kV networks of Siberia, which cover 23% of Russia's territory, are demonstrated in [11]; the results of the studies on parameters of harmonics for the complex loads connected to the nodes of the 110-220 kV networks are presented in [12]; the results of an analysis of harmonic active power of high-power nonlinear loads connected to the 110-220 kV networks are given in [13]. The measurements confirmed the presence of harmonics in the electrical networks.…”
Section: No 261-fz Of November 23 2009 "On Saving Energy and Increamentioning
The paper presents the results of the analysis on measured parameters of harmonics at the node of the high-voltage network. The measurements were made at the node connecting the pulp-and-paper mill to the 220 kV supply network. This load is nonlinear and has a large capacity. Particular attention is paid to the distributions of the current and voltage harmonics. The paper clearly shows probabilistic properties of the measured parameters of harmonics
“…In the last decade intensive measurements of harmonics parameters have been continued, which is explained by the emergence and widespread use of new nonlinear electric equipment and increase in the values of current and voltage harmonics in the networks. For example, the results of measurements at the network node supplying the nonlinear loads of the retransmission TV stations are presented in [8]; the results of measured parameters of the harmonics generated by energy saving lamps are presented in [9]; the harmonics measured in the medical center and their impact on the work of the medical equipment are indicated in [10]; the results of large-scale measurements of power quality indices in the 110 kV networks of Siberia, which cover 23% of Russia's territory, are demonstrated in [11]; the results of the studies on parameters of harmonics for the complex loads connected to the nodes of the 110-220 kV networks are presented in [12]; the results of an analysis of harmonic active power of high-power nonlinear loads connected to the 110-220 kV networks are given in [13]. The measurements confirmed the presence of harmonics in the electrical networks.…”
Section: No 261-fz Of November 23 2009 "On Saving Energy and Increamentioning
The paper presents the results of the analysis on measured parameters of harmonics at the node of the high-voltage network. The measurements were made at the node connecting the pulp-and-paper mill to the 220 kV supply network. This load is nonlinear and has a large capacity. Particular attention is paid to the distributions of the current and voltage harmonics. The paper clearly shows probabilistic properties of the measured parameters of harmonics
“…The previous analysis of measured data in [2], [6]- [8] shows that modeling a nonlinear load should include two stages:…”
Section: Supply Networkmentioning
confidence: 99%
“…For reactive current we assume the same direction as for reactive power in [11], provided the load is inductive. Active and reactive currents are directed from network to load if angle In [8] based on the analysis of measurements we obtained that at one and the same time instant active power of different harmonics can have opposite directions. This conclusion applies to currents as well.…”
Section: Analysis Of Directions Of Active and Reactive Harmonic Currentsmentioning
confidence: 99%
“…Duration of measurements should be determined individually for each certain case. Since the parameters of harmonic conditions in high-voltage networks vary randomly [6]- [8] it is necessary to analyze them by the methods of mathematical statistics.…”
Abstract. The paper presents an algorithm for modeling nonlinear loads connected to the nodes of high-voltage network. The algorithm is developed on the basis of measured parameters of harmonic conditions. The high-voltage networks are extended. Many nonlinear loads distributed across the territory of the region are connected to them. An analysis of measured parameters of harmonic conditions shows that they vary randomly. The algorithm for modeling the nonlinear loads is developed considering their probabilistic properties. The algorithm is illustrated with an example of modeling the nonlinear loads of a railway traction substation and an aluminum smelter shop that are powered by a 220 kV network.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.