Abstract:This paper presents an anti-windup (AW) proportional-integral (PI) secondary controller for both voltage and frequency restoration and stabilization for a stand-alone Microgrid (MG) system. The MG comprises four distributed generations (DGs) with distributed droop-based primary control systems and a centralized AW based secondary controller. The significance of this research is using a clamping model of the AW proportional-integral (AWPI) controller to suppress the possible overshoot or undershoot of the contr… Show more
Set email alert for when this publication receives citations?
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.