Abstract-This paper presents a novel control strategy for parallel inverters of distributed generation units in an ac distribution system. The proposed control technique, based on the droop control method, uses only locally measurable feedback signals. This method is usually applied to achieve good active and reactive power sharing when communication between the inverters is difficult due to its physical location. However, the conventional voltage and frequency droop methods of achieving load sharing have a slow and oscillating transient response. Moreover, there is no possibility to modify the transient response without the loss of power sharing precision or output-voltage and frequency accuracy. In this work, a great improvement in transient response is achieved by introducing power derivative-integral terms into a conventional droop scheme. Hence, better controllability of the system is obtained and, consequently, proper transient performance can be achieved. In addition, an instantaneous current control loop is also included in the novel controller to ensure proper sharing of harmonic components when supplying nonlinear loads. Simulation and experimental results are presented to prove the validity of this approach, which shows excellent performance as opposed to the conventional one.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.