In this paper, a novel and practical fault locator for radial distribution feeders is presented. The existing numerical relays of the MV panels are universally arranged in order to realize the proposed fault locator. This arrangement has been validated using an experimental set-up. The fault locator algorithm is carefully developed, modified, and intensively tested using the electromagnetic transient program (EMTP) for both phase and earth faults. Error correction of the computed fault distance via either rational or intelligent techniques is outlined. The results reveal a distinguished precision of the proposed fault locator. was working towards the Ph.D degree at Memorial University of Newfoundland (MUN), St. John's, Canada based on joint supervision with Menoufiya University. He has been involved in several pilot projects for the Egyptian industry for the design and implementation of numerical relays, SCADA, fault location in MV feeders, distribution management systems, protection training packages, and relay coordination. Dr. Darwish is currently an associate professor. His interests are in digital protection, signal processing, system automation, EMTP simulation, and switchgear.