Purpose: To identify the countermeasures and current status of disaster power outages in the radiology departments of hospitals. Methods: A web-based questionnaire survey of 600 hospitals nationwide was conducted. The questionnaire survey covered 34 items, including availability of power in the radiology department in the event of a disaster and the impact of power outages on medical equipment in the radiology department. Results: In all, 242 facilities (40.3%) responded to our survey. During power outages, 55.8%-68.2% of facilities were able to use CT, digital radiography, and angiography systems with their private generators. In 28.1%-40.7% of facilities, medical information systems were not available in all laboratories. In addition, power outages caused equipment malfunctions in 81.4% of facilities radiology departments. Conclusion: We have identified the power supplied by private generators to the radiology department s medical equipment and medical information systems. Many medical equipment have malfunctioned due to power outages. Therefore, drills should be conducted to simulate various situations caused by power outages.