An important requirement of the power grid with high penetration of renewable energy sources is the mitigation of potential harmonic interactions between different distributed large grid-tie inverters and the mains. This work presents the harmonic interaction between multiple multilevel photovoltaic (PV) inverters based on the well-known T-type neutral-point-clamped inverter (3L-TNPC). The multiple 3L-TNPC is connected in parallel to a common ac bus by using distribution voltage feeders. The analysis is performed by using the Norton equivalence model of each power circuit, its admittance matrix modeling, and the potential overall impedance resonances with the ac grid. The main contribution of this work is the development of a current harmonic injection model of the system operating under a polluted voltage grid for harmonic analysis, while overall filtering design restrictions due to impedance limits based on current and voltage standards are considered. The proposed impedance Norton model is compared with the electromagnetic transient model (EMT model) by using comprehensive simulations, showing good match between both models.