Analysis of frequent alarms for commutation failure prevention of a ±800kV inverter station

Yanru Li,
Wuhao Zhao,
Gang Li
et al.

Abstract: After a ±800kV inverter station is put into operation, there are frequent alarms of Commutation Failure Prevention when one AC filter is put into operation. And the fault recording showed that the zero-sequence voltage fluctuated greatly. In view of this phenomenon, this paper introduces and analyzes the principle of commutation failure prevention of the inverter station. Combining with the fault recording results, it is determined that the cause of commutation failure to predict frequent action is that the ca… Show more